ASTRID2 automation
Status:
This documentation applies to version 1.47.740.76 (30/4-2024) of the VdAstrid2/CVdAst2Automation device.
Contents:
- CVdAst2Automation overview
- Automation device
- ASTRID2 error fix scheduler device
- ASTRID2 error fix device
- VdAstrid2
- A0: A2 MachineMode auto change
CVdAst2Automation Overview:
Automations for ASTRID2 are implemented in this device.
A0: A2 MachineMode auto change
AUT100MchnMdAutoAst2
Trigger:
When OpMode change, Machine mode change, A1 og A2 hall opened change and every hour
Action:
- When entering User mode, MachineMode should be set to OnAutoRecovery
- When entering MachinePhys mode and MachineMode is in OnAutoRecovery, MachineMode should be set to OnBasicAuto
- If AutomationAst2.McnModeAutoChn18 is true when in MachinePhysics:
- If MachineMode is in OnBasicAuto, and both Accelerator Halls are closed MachineMode should be set to OnAutoRecovery at 18:00
- If MachineMode changed to OnAutoRecovery the evening before, MachineMode should be set to OnBasicAuto at 08:00 on Weekdays
- If either accelerator halls are opened when MachineMode is in OnAutoRecovery MachineMode is set to OnBasicAuto
- When both halls are closed again, the MachineMode goes back to OnAutoRecovery (if it was in OnAutoRecovery before halls being opened AND if the MachineMode has not manually being changed during the open hall period - and if we have not changed from UserMode)
Last Modified 03 May 2024